| Technical parameter | Practical classification |
|---|---|
| Standard basis | IEC 61131-3 |
| Programming languages | ST, FUP, KOP, AWL |
| Architecture | Modular encapsulation / object orientation |
| Cycle time | 10 ms - 50 ms (depending on application) |
| Diagnostic depth | Standard error messages |
| Maintenance access | High reusability through libraries |
| Security | Standard level (no PL/SIL) |
| Data connection | OPC UA, Profinet IO |
| Scalability | High thanks to modular components |
| Areas of application | Conveyor technology, packaging machines |
| Economic efficiency | Focus on short engineering times |
| Special features | Separation of process and administration level |
| Technical parameter | Practical classification |
|---|---|
| Standard basis | EN ISO 13849, IEC 62061 |
| Performance level | Up to PL e / SIL 3 |
| Logical rigor | Deterministic (no dynamic allocation) |
| Response time | Critical (typically < 20ms depending on application)/td> |
| Security matrix | Subject to validation |
| Diagnostic depth | Maximum (hardware and software errors) |
| Fault tolerance | Two-channel structure / diversity |
| Communication | PROFIsafe, FSoE (Fail Safe over EtherCAT) |
| Maintenance | Certified access required |
| Areas of application | Pharmaceuticals, chemicals, hazardous areas |
| Economic efficiency | Higher engineering costs due to validation |
| Special features | Strict separation of standard vs. safety |
| Technical parameter | Practical classification |
|---|---|
| Focus | Dynamics / Synchronization |
| Cycle time | < 1 ms (real-time requirement)/td> |
| Communication system | EtherCAT, Profinet IRT |
| Control algorithm | PID, interpolation, cam plates |
| Number of axles | Multi-axis systems (up to > 64 axes) |
| Jitter | Minimized (in the µs range) |
| Data load | High (continuous status updates) |
| Programming focus | Performance optimization |
| Hardware | High-end PLC or IPC-based control system |
| Areas of application | Automotive, robotics, high-speed handling |
| Economic efficiency | High initial costs due to hardware requirements |
| Special features | Time-critical deterministic runtime |
| Technical parameter | Practical classification |
|---|---|
| Architecture | Hot standby / redundancy (1oo2) |
| Synchronization | Real-time data mirroring (LWL) |
| Switchover time | < 10 ms (seamless)/td> |
| Programming focus | Consistent data management / state preservation |
| Fault tolerance | High (single fault safe) |
| Diagnostic depth | System-wide health check of both CPUs |
| Hardware | Special redundancy-capable controllers |
| Data loss | Zero (with correct design) |
| Areas of application | Energy technology, chemistry, water management |
| Economic efficiency | Highest CAPEX (hardware + engineering) |
| Special features | Master/slave management required |
| Technical parameter | Practical classification |
|---|---|
| Design | Monolithic / Compact |
| Resources | Limited (RAM/ROM) |
| Programming focus | Performance optimization (code footprint) |
| Communication | Simple fieldbuses (Modbus/IO-Link) |
| Modularity | Low to moderate |
| Hardware | Compact controller with integrated I/Os |
| Engineering effort | Low |
| Scalability | Restricted |
| Areas of application | Small machines, toolmaking, OEM components |
| Economic efficiency | Excellent (low hardware costs) |
| Special features | Hardware-oriented programming preferred |